TMA IS Equipment General Description

Requested by:

Ghesa

Doc. Code:

3151_MCS_0008

Editor:

Julen

Approved by:

Alberto

Introduction

This document contains the general equipment description of the TMA interlock system, based on the PSS4000 series by PILZ.

Reference documents

Document

Code

Version

1

Safety Review and Hazard Analysis

092-308-E-Z-00001

(Draft 2)

2

LSST Summit Safety Interlock System

LTS-99

3

Telescope Mount Assembly to Interlock System Interface Control Document”

LTS-173

4

TMA Safety Hazard Analysis 24-04-2013

14428

V2

5

TMA IS HW Design Report

3151_MCS_0007

3.0

6

MCS Equipment General Description

3151_MCS_0004

3.0

Safety Hardware

This section includes the main characteristics of the hardware devices used in the TMA IS hardware configuration, which are based on PILZ devices.

PILZ PSS 4000 Universal

The hardware shown in the following chapter is the solution adopted to manage all the safety on the TMA. This solution is based on the PSS4000 family. There is one main Failsafe CPU in the main cabinet, with local I/Os on the same rack, and inputs and outputs distributed in the auxiliary cabinets connected to the main CPU via PILZ proprietary SafetyNET network.

Safety CPU PSSu H PLC1 FS SN SD-T

This is a Safety CPU with two SafetyNET connections. Used on the main cabinet, as the principal safety controller.

It can be expandable with safe and standard inputs and outputs on its right side.

Safety CPU

The head module belongs to the performance class “Control system PSSu PLC”. It can be used to connect a PSSu system to a SafetyNET p. The head module has the following features:

  • 2 free switch ports for connection to SafetyNET p

  • One FS resource and one ST resource

  • SD card used to store the device project and the naming data

  • Reset button

    • For warm reset

    • To transfer the naming data and/or device project from the SD card to the device memory

  • Supply voltage

    • Integrated supply voltage for periphery supply and module supply

    • Module supply is buffered for 20 ms if the supply voltage is interrupted

    • Plug­in connection terminals (either spring­loaded terminal or screw terminal)

  • Status LEDs

  • Supports FS and ST modules

  • T-type for increased environmental requirements

Technical details for PSS 4000 CPU

General

Approvals

BG, CE, EAC (Eurasian), GOST, TÜV, cULus Listed

Application range

Standard / failsafe

System sections

314070

ST resource

Yes

FS resource

Yes

ST module bus

Yes

FS module bus

Yes

ST SNp interface

Yes

FS SNp interface

Yes

PROFIBUS­DP Slave

No

IP Connections

Yes

EtherNet/IP adapter

Yes

Diagnostic Server

No

OPC Server

No

Programming

IEC 61131 programming

Yes

Multi programming

Yes

Non­volatile variables

Yes

Supply voltage for

Module supply

Voltage

24,0 V

Kind

DC

Voltage tolerance

­30 %/+25 %

Max. continuous current that the external power supply must provide

1,0 A

Output of external power supply (DC)

16,0 W

Supply voltage for

Periphery supply

Voltage

24 V

Kind

DC

Voltage tolerance

­30 %/+25 %

Max. continuous current that the external power supply must provide

10,0 A

Potential isolation between module supply and periphery supply

3050 V

Electrical data

Internal supply voltage (module supply)

Output voltage

int. system

Voltage

5 V

Voltage tolerance

­2 %/+3 %

Potential isolation

3050 V

Current load capacity

2,0 A

Buffer in the case of supply interruptions in accordance with

EN 61131­2, EN 61496­1

Short circuit­proof

Yes

CPU

Real­time clock for time and date, buffered

Resolution

1 s

Deviation

+/­ 10s/Day

Buffer time

10 days

Max. number of FS tasks

9

Max. number of ST tasks

9

Max. number of variables with elementary data types on the FS resource

10.000

Max. number of variables with elementary data types on the ST resource

10.000

Min. cycle time, FS tasks

6 ms

Min. cycle time, ST tasks

2 ms

Working memory (RAM)

128 MB

Memory for the user program per resource

4 MB

Removable data medium

Type

SD card

External communication

Max. number of IP connections

32

Modbus/TCP Cycle time (t_ExtCo)

2…2 000 000 ms

Raw UDP Cycle time (t_ExtCo)

2…2 000 000 ms

SafetyNET p interface

Number

2

IP address (automatically off)

169.254.X.Y

Connection

RJ45

Transmission rates

100 MBit/s

Set via

automatic

Max. number of FS-Tx and FS-Rx connections

64

Max. number of ST-Tx and ST-Rx connections

64

Cycle time (t_SNp)

2…60000ms

Max. number of variables with elementary ST data types

5000

Max. number of variables with elementary FS data types

4000

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

Temperature range

-40 ­ 70 °C

Storage temperature

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 55,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Number of shocks

6

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­27

Number of shocks

1000

Acceleration

10g

Duration

16 ms

Max. operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664­1

OverVoltage category

II

Pollution degree

2

Protection type

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Mechanical data

Material

Bottom

PC

Connection type

Spring­loaded terminal, screw terminal

Mounting type

plug­in

Conductor cross section with screw terminals

1 core flexible

0,25 ­ 2,50 mm², 24 ­ 12 AWG

2 core with the same cross section, flexible with crimp connectors, no plastic sleeve

0,25 ­ 1,00 mm², 24 ­ 16 AWG

2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors

0,20 ­ 1,50 mm², 24 ­ 16 AWG

Torque setting with screw terminals

0,50 Nm

Conductor cross section with spring­loaded terminals:

Flexible with/without crimp connector

0,20 ­ 2,50 mm², 24 ­ 12 AWG

Stripping length with spring­loaded terminals

9,0 mm

Dimensions

Height

125,6 mm

Width

130,0 mm

Depth

83,7 mm

Weight

378 g

Safety characteristic data

EN ISO mode 13849­1: 2008 PL

PL e

EN ISO 13849­1: 2008 Category

Cat. 4

EN 62061 SIL CL

SIL CL 3

EN 62061 PFH [1/h]

4,14E-9

IEC 61511 SIL

SIL 3

IEC 61511 PFD

3,51E-5

EN ISO 13849­1: 2008 TM [year]

20

Safety I/O PSSu H FS SN SD-T

This is a distributed I/Os with two SafetyNET connections. It can be expandable with safe and standard inputs and outputs on its right side.

Safety Remote IOs

The head module belongs to the performance class “Decentralised system PSSu I/O”. It can be used to connect a PSSu system to SafetyNET p. The head module has the following features:

  • 2 free switch ports for connection to SafetyNET p

  • Standard module bus for standard I/O modules

  • SD card used to store the device project and the naming data

  • Supply voltage

    • Integrated supply voltage for periphery supply and module supply

    • Module supply is buffered for 20 ms if the supply voltage is interrupted

    • Plug­in connection terminals (either spring­loaded terminal or screw terminal)

  • Status LEDs

  • T-type for increased environmental requirements

Technical details for PSSu H FS SN SD-T

General 314085

Approvals

BG, CE, EAC (Eurasian), GOST, TÜV, cULus Listed

Application range

Standard / failsafe

System sections 314085

ST resource

No

FS resource

No

ST module bus

Yes

FS module bus

Yes

ST SNp interface

Yes

FS SNp interface

Yes

PROFIBUS­DP Slave

No

IP Connections

No

Diagnostic Server

No

OPC Server

No

Programming

IEC 61131 programming

No

Multi programming

No

Non­volatile variables

No

Supply voltage for

Module supply

Voltage

24,0 V

Kind

DC

Voltage tolerance

­30 %/+25 %

Max. continuous current that the external power supply must provide

1,0 A

Output of external power supply (DC)

16,0 W

Supply voltage for

Periphery supply

Voltage

24 V

Kind

DC

Voltage tolerance

­30 %/+25 %

Max. continuous current that the external power supply must provide

10,0 A

Potential isolation between module supply and periphery supply

3050 V

Electrical data

Internal supply voltage (module supply)

Output voltage

int. system

Voltage

5 V

Voltage tolerance

­2 %/+3 %

Potential isolation

3050 V

Current load capacity

2,0 A

Buffer in the case of supply interruptions in accordance with

EN 61131­2, EN 61496­1

Short circuit­proof

Yes

CPU

Real­time clock for time and date, buffered

Resolution

1 s

Deviation

+/­ 10s/Day

Buffer time

10 days

Working memory (RAM)

64 MB

Removable data medium

Type

SD card

External communication

Max. number of IP connections

32

Modbus/TCP Cycle time (t_ExtCo)

2…2 000 000 ms

Raw UDP Cycle time (t_ExtCo)

2…2 000 000 ms

SafetyNET p interface

Number

2

IP address (automatically off)

169.254.X.Y

Connection

RJ45

Transmission rates

100 MBit/s

Set via

automatic

Max. number of FS-Tx and FS-Rx connections

64

Max. number of ST-Tx and ST-Rx connections

64

Cycle time (t_SNp)

2…60000ms

Max. number of variables with elementary ST data types

5000

Max. number of variables with elementary FS data types

4000

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

Temperature range

-40 ­ 70 °C

Storage temperature

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 55,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Number of shocks

6

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­27

Number of shocks

1000

Acceleration

10g

Duration

16 ms

Max. operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664­1

OverVoltage category

II

Pollution degree

2

Protection type

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Mechanical data

Material

Bottom

PC

Connection type

Spring­loaded terminal, screw terminal

Mounting type

plug­in

Conductor cross section with screw terminals

1 core flexible

0,25 ­ 2,50 mm², 24 ­ 12 AWG

2 core with the same cross section, flexible with crimp connectors, no plastic sleeve

0,25 ­ 1,00 mm², 24 ­ 16 AWG

2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors

0,20 ­ 1,50 mm², 24 ­ 16 AWG

Torque setting with screw terminals

0,50 Nm

Conductor cross section with spring­loaded terminals:

Flexible with/without crimp connector

0,20 ­ 2,50 mm², 24 ­ 12 AWG

Stripping length with spring­loaded terminals

9,0 mm

Dimensions

Height

125,6 mm

Width

130,0 mm

Depth

83,7 mm

Weight

378 g

Safety characteristic data

EN ISO mode 13849­1: 2008 PL

PL e

EN ISO 13849­1: 2008 Category

Cat. 4

EN 62061 SIL CL

SIL CL 3

EN 62061 PFH [1/h]

4,14E-9

IEC 61511 SIL

SIL 3

IEC 61511 PFD

3,51E-5

EN ISO 13849­1: 2008 TM [year]

20

Digital input module: PSSu EF 4DI-T

A 4 safety digital input module.

4 Failsafe Digital Inputs

The product has the following features:

  • 4 digital inputs

  • 2 test pulse outputs, with the option to configure them as:

    • Independent test pulse outputs that use different test pulses (periphery supply)

    • Outputs with constant voltage (periphery supply)

  • LEDs for:

    • Switch status of each input

    • Module error

  • T-type for increased environmental requirements

  • For failsafe applications in system environments A and B

Technical details for PSSu E F 4 DI-T

General

314200

Approvals

BG, CE, EAC (Eurasian), KOSHA, TÜV, cULus Listed

Application Range

Failsafe

Module’s device code

0A00h

Number of FS input bits

4

Application in system environment A

From FS firmware version, other head modules

4

From FS firmware version PSSu H F PN

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

23 mA

Module’s power consumption

0,12 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30 V

Module’s current consumption with no load

8 mA

Module’s power consumption with no load

0,19 W

Max. power dissipation of module

1,5 W

Inputs

Number

4

Voltage at inputs

24 V DC

Input current at rated voltage

6 mA

Input current range

2,6 ­ 7,8 mA

Min. threshold voltage when signal changes from “1” to “0”

9 V

Max. threshold voltage when signal changes from “0” to “1”

10 V

Max. processing time of input when signal changes from “1” to “0”

1 ms

Max. processing time of input when signal changes from “0” to “1”

1 ms

Min. processing time of in­ put when signal changes from “1” to “0”

0,5 ms

Min. processing time of in­ put when signal changes from “0” to “1”

0,5 ms

Potential isolation between input and internal module bus voltage

Yes

Test pulse outputs

Number of test pulse outputs

2

Voltage, test pulse outputs

24 V DC

Short circuit proof

Yes

Number of outputs that can be configured as test pulses

2

Max. output current at “1” signal

0,25 A

Max. cable length between test pulse output and input

200 m

Standard for voltage interruptions

EN61131­2, EN61496­1

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 60 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068-2-30, EN 60068-2-78

Humidity

93 % r. h. at 40ºC

Condensation during operation

Short term

EMC

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-6-2, EN 61000-6-4

Vibration

In accordance with the standard

EN 60068-2-6

Frequency

10 – 150 Hz

Amplitude

0,35 mm

Acceleration

1 g

Shock stress

In accordance with the standard

EN 60068-2-27

Number of shocks

6

Acceleration

15 g

Duration

11 ms

In accordance with the standard

EN 60068-2-27

Number of shocks

1000

Acceleration

10 g

Duration

16 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76 mm

Width

12,6 mm

Depth

60,2 mm

Weight

36 g

Mechanical coding

Type

D

Color

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

1-­channel

PL d

Cat. 2

SIL CL 2

9,00E-9

SIL 2

7,89E­-4

20

2-channel

PL e

Cat. 4

SIL CL 3

3,10E-9

SIL 3

1,85E-5

20

2­ch. pulsed

PL e

Cat. 4

SIL CL 3

3,10E-9

SIL 3

1,85E­-5

20

1-ch., pulsed light barrier

PL e

Cat. 4

SIL CL 3

2,91E-9

SIL 3

7,52E-5

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Digital output module: PSSu E F 4DO 0.5-T

4 safe digital output module, with maximum 0.5 A each output

E F 4DO 0.5

Figure 4 - E F 4DO 0.5

The product has the following features:

  • 4 Digital outputs

    • Semiconductor technology

    • Single pole

    • Positive switching

    • Current load capacity per output: 0,50 A

    • Short circuit proof

    • Overload proof

    • Free from feed

  • LEDs

  • Switch status per ou

    • FS enable per output

    • Module e

  • For failsafe applications in system environment A and B

  • T-type for increased environmental requirements

Technical details for PSSuE F 4DO 0.5

General

314210

Approvals

BG, CE, GOST, TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0C01h

Number of FS output bits

4

Application in system environment A

From FS firmware version, other head modules

4

From FS firmware version PSSu H F PN

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

56 mA

Module’s power consumption

0,28 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

37 mA

Module’s power consumption with no load

0,90 W

Max. power dissipation of module

1,50 W

Terminal voltage when switching off inductive loads

U2 ­ 50 V

Permitted loads

inductive, capacitive, resistive

Semiconductor outputs

Number of positive­ switching single­pole semiconductor outputs

4

Voltage

24 V DC

Typ. output current at “1” signal and rated voltage of semiconductor output

0,50 A

Permitted current range

0,00 ­ 0,62 A

Residual current at “0” signal

0,02 mA

Max. transient pulsed current

6 A

Max. internal voltage drop

300 mV

Monitoring threshold of semiconductor output

6,0 V

Max. duration of on time during self test

200 µs

Max. duration of off time during self test

350 µs

Max. processing time of semiconductor output when signal changes from “1” to “0”

0,020 ms

Max. processing time of semiconductor output when signal changes from “0” to “1”

0,010 ms

Potential isolation from system voltage

Yes

Short circuit­proof

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­30, EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 150,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­29

Acceleration

10g

Duration

16 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76 mm

Width

12,6 mm

Depth

60,2 mm

Weight

38 g

Mechanical coding

Type

E

Color

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

1-­channel

PL d

Cat. 2

SIL CL 2

9,00E-9

SIL 2

7,89E­-4

20

2-channel

PL e

Cat. 4

SIL CL 3

1,13E-9

SIL 3

1,66E-5

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Digital output module: PSSu E F 2DO 2-T

Two safe digital output module, with maximum 2 A for each output.

2A output module

The product has the following features:

  • 2 Digital outputs

    • Semiconductor technology

    • Single pole

    • Positive switching

    • Current load capacity per output: 2,00 A

    • Short circuit proof

    • Overload proof

    • Free from feedback

  • LEDs

  • Switch status per output

    • FS enable per output

    • Module error

  • For failsafe applications in system environment A and B

  • T-type for increased environmental requirements

Technical details for PSSu E F 2DO 2

General

312215

Approvals

BG, CE, GOST, TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0C00h

Number of FS output bits

2

Application in system environment A

From FS firmware version, other head modules

4

From FS firmware version PSSu H F PN

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

45 mA

Module’s power consumption

0,23 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

30 mA

Module’s power consumption with no load

0,72 W

Max. power dissipation of module

1,50 W

Terminal voltage when switching off inductive loads

U2 ­ 50 V

Permitted loads

inductive, capacitive, resistive

Semiconductor outputs

Number of positive­ switching single pole semiconductor outputs

2

Voltage

24 V DC

Typ. output current at “1” signal and rated voltage of semiconductor output

2,00 A

Permitted current range

0,00 ­ 2,50 A

Residual current at “0” signal

0,02 mA

Max. transient pulsed cur­ rent

12 A

Max. internal voltage drop

250 mV

Monitoring threshold of semiconductor output

6,0 V

Max. duration of on time during self test

200 µs

Max. duration of off time during self test

350 µs

Max. processing time of semiconductor output when signal changes from “1” to “0”

0,020 ms

Max. processing time of semiconductor output when signal changes from “0” to “1”

0,010 ms

Potential isolation from system voltage

Yes

Short circuit proof

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­30, EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 150,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­29

Acceleration

10g

Duration

16 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76,0 mm

Width

12,6 mm

Depth

60,2 mm

Weight

36 g

Mechanical coding

Type

F

Color

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

1-­channel

PL d

Cat. 2

SIL CL 2

9,00E-9

SIL 2

7,89E­-4

20

2-channel

PL e

Cat. 4

SIL CL 3

1,13E-9

SIL 3

1,66E-5

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Digital output module: PSSu E F 2DOR 8-T

Two safe digital output module, with maximum 8 A each output.

8A output module

The product has the following features:

  • 2 Relay contacts

    • N/O contact – Voltage free – Current load capacity per output: 8 A

  • LEDs for: – Switch status of each output – Module error

  • For failsafe applications in system environment A and B

  • T-type:

    • PSSu E F 2DOR 8T: for increased environmental requirements

  • R-type:

    • PSSu E F 2DOR 8R: for railway applications

Technical details for PSSu E F 2DOR 8-T

General

314225

Approvals

BG, CE, EAC, KOSHA, TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0C03h

Number of FS output bits

2

Application in system environment A

From FS firmware version, other head modules

4

From FS firmware version PSSu H F PN

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

40 mA

Module’s power consumption

0,2 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

60 mA

Module’s power consumption with no load

1,5 W

Max. power dissipation of module

2,50 W

Max. inrush current at UB

1A

Permitted loads

inductive, resistive

Relay outputs

Number of relay outputs

2

Utilization category in accordance AC1 at Min current Max current Max power AC1 with condensation at Min current Max current Max power DC1 at Min current Max current Max power

EN 60947-4-1 250V 10mA 8A 2000 VA 30V 10mA 8A 240VA 24V 10mA 9A 192W

External contact fuse protection, safety contacts In accordance with the standard Blowout fuse, quick Blowout fuse, slow

VDE 0660 10 A 6 A

Max. processing time of relay output when signal changes from “1” to “0”

120ms

Max. processing time of relay output when signal changes from “0” to “1”

60ms

Contact material

AgCuNi + 0,2 μm Au

Potential isolation between relay contact and module supply

4900 V (prot. separation)

Potential isolation between relay contact and Crail

3050 V (basic insulation)

Potential isolation between relay contact 1 and relay contact 2

4900 V (prot. separation)

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­30, EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 150,0 Hz

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­29

Acceleration

10g

Duration

16 ms

Max operating height above sea level

2000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

III

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Mechanical life

10,000,000 cycles

Dimensions

Height

76,0 mm

Width

25,2 mm

Depth

60,2 mm

Weight

90g

Mechanical coding

Type

H

Calor

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

1-­channel

PL c

Cat. 1

7,60E-8

6,66E­-3

20

2-channel

PL e

Cat. 4

SIL CL 3

7,78E-10

SIL 3

1,34E-6

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Analog input module: PSSu E F AI U-T

One safe analog voltage input module

Safe Analog Input Module

The product has the following features:

  • 1 Analogue voltage input

  • Voltage range: -­10.24 V … +10.2375 V Dual­pole, differential input

  • Resolution: 13 Bit (representation of negative values in the two’s complement)

  • LEDs for:

    • Operating status per input

    • Module error

  • For failsafe applications in system environment B (automation system PSS 4000)

  • T-type for increased environmental requirements

Technical details for PSSu E F AI U

General

314265

Approvals

BG, CE, EAC (Eurasian), TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0B00h

Number of FS input bits

16

Number of FS status bits

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

45 mA

Module’s power consumption

0,22 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

34 mA

Module’s power consumption with no load

0,58 W

Max. power dissipation of module

0,80 W

Analogue inputs

Number of analogue in­ puts

1

Type of analogue inputs

Voltage

Input area

­10.24 V … +10.2375 V

Input filter

RC filter

Cutoff frequency

82 Hz

Voltage measurement

Value of least significant bit (LSB)

2,5 mV

Input resistance

57 kOhm

Max. continuous voltage

60 V

Resolution (without sign bit)

13 Bit

Max. common mode voltage

40 V

Safety­related accuracy (1 input)

5 %

Deviations from the measuring range limit value

Linearity error

0,05 %

Output variable error at 25 °C

0,4 %

Temperature coefficient

0,0030 %/K

Max. measurement error during EMC test

1,0 %

Potential isolation between input and periphery supply

Yes

Inputs

Potential isolation between input and internal module bus voltage

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic Suitability

In accordance with the standard

EN 60068-2-30, EN 60068-2-78

Humidity

93% r. h. at 40 ºC

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 150,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Number of shocks

6

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­27

Number of shocks

1000

Acceleration

10g

Duration

16 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom Front Coding

PC PC PA

Mounting type

plug­in

Dimensions

Height Width Depth

76,0 mm 12,6 mm 60,2 mm

Weight

38 g

Mechanical coding

Type Calor

M Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

2-channel

PL e

Cat. 4

SIL CL 3

4,37E-9

SIL 3

2,99E-5

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Analog input module: PSSu E F AI I-T

One safe analog current input module

Safe Analog Input Module

The product has the following features:

  • 1 Analogue current input

  • Current range: 0 … 25.59375 mA Dual­pole, differential input

  • Resolution: 12 Bit (representation of negative values in the two’s complement)

  • LEDs for:

    • Operating status per input

    • Module error

  • For failsafe applications in system environment B (automation system PSS 4000)

  • T-type for increased environmental requirements

Technical details for PSSu E F AI I

General

314260

Approvals

BG, CE, GOST, TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0B10h

Number of FS input bits

16

Number of FS status bits

1

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current con­ sumption

45 mA

Module’s power con­ sumption

0,22 W

Periphery’s supply voltage (periphery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

34 mA

Module’s power consumption with no load

0,58 W

Max. power dissipation of module

0,80 W

Analogue inputs

Number of analogue inputs

1

Type of analogue inputs

Current

Input area

0 … 25.59375 mA

Input filter

RC filter

Cutoff frequency

71 Hz

Current measurement

Value of least significant bit (LSB)

6,25 µA

Input resistance

115,000 Ohm

Max. continuous current

40 mA

Resolution (without sign bit)

12 Bit

Safety­related accuracy (1 input)

5 %

Deviations from the measuring range limit value

Linearity error

0,05 %

Output variable error at 25 °C

0,4 %

Temperature coefficient

0,0030 %/K

Max. measurement error during EMC test

1,0 %

Potential isolation between input and periphery supply

Yes

Inputs

Potential isolation between input and internal module bus voltage

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­30, EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

Short term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 150,0 Hz

Amplitude

0,35 mm

Acceleration

1g

Shock stress

In accordance with the standard

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­29

Acceleration

10g

Duration

16 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76,0 mm

Width

12,6 mm

Depth

60,2 mm

Weight

38 g

Mechanical coding

Type

K

Calor

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

1-­channel

SIL CL 2

1,56E-8

SIL 2

1,37E­-3

20

2-channel

PL e

Cat. 4

SIL CL 3

4,37E-9

SIL 3

2,99E-5

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Power Supply PSSu E F PS-T

The product has the following features:

  • Power supply for max. 1.5 A

  • The module supply is not buffered if the supply voltage is interrupted

  • Separate infeed for periphery supply

  • Separate infeed for module supply

  • Infeed for C-rail supply

  • LEDs for:

    • Module supply

    • Periphery supply

    • Module error

  • Application range depends on the base module

  • T-type for increased environmental requirements

Technical details for PSSu E F PS

Technical details 314190

Application range

Standard/Failsafe

Module’s device code

0801h

Support in system environment A

from FS firmware version for other head modules

4

from ST firmware version for other head modules

5

from FS firmware version PSSu H F PN

1

from ST firmware version PSSu H S PN

1

from ST firmware version PSSu WR S IDN

6

Support in system environment B

from head module FS firmware version

1 0.0

from head module ST firmware version

1.0.0

Electrical data

Infeed for

Module Supply

Voltage

24 V DC

Voltage tolerance

-30 %/+25 %

Output of external power supply (DC)

9.0 W

Max. continuous current that the external power supply must provide

0.6 A

Inrush current that the external power supply must provide

4.0 A

Module’s current consumption

23 mA

Module’s power consumption

0.12 W

Infeed for

Periphery Supply

Voltage

24 V DC

Voltage tolerance

-30 %/+25 %

Max. continuous current that the external power supply must provide

10.0 A

Voltage output

Module Supply

Voltage

5 V DC

Voltage tolerance

-2 %/+3 %

Current load capacity

1.5 A

Short circuit-proof

Yes

Potential isolation between input and internal module bus voltage

3050 V

Max. Power dissipation of the module

1.50 W

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature

In accordance with the standard

EN 60068­2­14

Temperature range

-40 ­ 70 °C

Max. ambient temperature in accordance with UL508

60 ºC

Storage temperature

In accordance with the standard

EN 60068­2­1/­2

Temperature range

­40 ­ 70 °C

Climatic suitability

In accordance with the standard

EN 60068­2­30, EN 60068­2­78

Humidity

93 % r. h. at 40 °C

Condensation during operation

no

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 1000,0 Hz

Amplitude

0,35 mm

Acceleration

5g

Shock stress

In accordance with the standard

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­29

Acceleration

25g

Duration

5 ms

Max operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664-1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Mechanical data

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76,0 mm

Width

12,6 mm

Depth

60,2 mm

Weight

41 g

Mechanical coding

Type

B

Calor

Yellow

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Incremental Encoder Input PSSu E F INC-T

Incremental Encoder Input Module

The product has the following features:

  • Inputs for – Counter pulses (inputs A, B) – Zero pulse (input C) – Stopping the counter (input G, Gate) – Memory function (Input L, Latch) – Rotary encoder status (Input S, Status)

  • Resolution of the counter and latch memory: 32 Bit

  • Operating modes: – Incremental encoder – Counter

  • Inputs A, B, C are operated as differential inputs with inverted signals (A,B,C).

  • LEDs for: – Data transfer per input A, B, C – Status per functional input (Gate, Latch, Status) – Module error

  • For failsafe applications in system environment B (automation system PSS 4000)

  • T-type for increased environmental requirements

Technical details for PSSu E F INC-T

General 314280

Approvals

BG, CE, GOST, TÜV, cULus Listed

Application range

Failsafe

Module’s device code

0324h

Number of ST input bits

64

Number of ST output bits

32

Number of ST control bits

8

Number of ST status bits

8

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Module’s power consumption

0,79 W

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

157 mA

Periphery’s supply voltage (peri­ phery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

15 mA

Module’s power consumption with no load

0,37 W

Max. power dissipation of module

1,20 W

Incremental encoder input

Number of counter inputs

1

Type of counter inputs

Incremental encoder

Signal at counter inputs A and B and/or C

Differential signal (RS 422)

Permitted low signal range on LATCH/GATE/STATUS signals

-3 -5V Bit

Permitted high signal range on LATCH/GATE/STATUS signals

11 30V

Typ. input current of the LATCH and/or GATE and/or STATUS signals at low level

0 mA

Typ. input current of the LATCH and/or GATE and/or STATUS signals at high level

4,0 mA

Max. number of bits on the counter input

32

Evaluation of counter pulses

1x

Phase offset between differential signals

90 deg

Phase offset tolerance

30 deg

Maximum cutoff frequency

5,0 MHz

Time constant of input filter on LATCH signal

50 µs

Time constant of input filter on GATE signal

50 µs

Time constant of input filter on STATUS signal

50 µs

Typ. processing time

0,1ms

Potential isolation between input/ output and periphery supply

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature In accordance with the standard Temperature range

EN 60068­2­14 -40 ­ 70 °C

Storage temperature In accordance with the standard Temperature range

EN 60068­2­1/­2 ­40 ­ 70 °C

Climatic suitability In accordance with the standard Humidity

EN 60068­2­30, EN 60068­2­78 93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 1000,0 Hz

Amplitude

0,35 mm

Acceleration

5g

Broadband noise

In accordance with the standard

EN 60068-2-64

Frequency

5-500 Hz

Acceleration

1.9g_rms

Shock stress

In accordance with the standard EN 60068­2­27

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­27

Acceleration

25g

Duration

6 ms

Max. operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664­1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76,0 mm

Width

25,4 mm

Depth

60,2 mm

Weight

51 g

Mechanical coding

Type

J

Calor

Yellow

Safety characteristic data

Operating mode

EN ISO 13849­1: 2008 PL

EN ISO 13849­1: 2008 Category

EN 62061 SIL CL

EN 62061 PFH [1/h]

IEC 61511 SIL

IEC 61511 PFD

EN ISO 13849­1: 2008 TM [year]

PL e

Cat. 4

SIL CL 3

3,34E-9

SIL 3

5,62E­-6

20

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Standard Incremental Encoder Input PSSu E S INC-T

Standard Incremental Encoder Input Module

The product has the following features:

  • Inputs for – Counter pulses (inputs A, B) – Zero pulse (input C) – Stopping the counter (input G, Gate) – Memory function (Input L, Latch) – Rotary encoder status (Input S, Status)

  • Resolution of the counter and latch memory: 32 Bit

  • Operating modes:

    • Incremental encoder

    • Counter

  • Inputs A, B, C are operated as differential inputs with inverted signals (A-,B-,C-). Pulse multiplication (up to four times)

  • LEDs for:

    • Data transfer per input A, B, C – Status per functional input (Gate, Latch, Status) – Module error

  • For standard applications in system environment B (automation system PSS 4000)

  • T-type for increased environmental requirements

Technical details for PSSu E S INC-T

General 314485

Approvals

CE, cULus Listed

Application range

Standard

Module’s device code

0321h

Number of ST input bits

64

Number of ST output bits

32

Number of ST control bits

8

Number of ST status bits

8

Application in system environment B

From FS firmware version, head modules

1.0.0

Electrical data

Internal supply voltage (module supply)

Module’s power consumption

0,79 W

Supply voltage range of module supply

4,8 ­ 5,4 V

Module’s current consumption

157 mA

Periphery’s supply voltage (peri­ phery supply)

Voltage range

16,8 ­ 30,0 V

Module’s current consumption with no load

15 mA

Module’s power consumption with no load

0,37 W

Max. power dissipation of module

1,20 W

Incremental encoder input

Number of counter inputs

1

Type of counter inputs

Incremental encoder

Signal at counter inputs A and B and/or C

Differential signal (RS 422)

Permitted low signal range on LATCH/GATE/STATUS signals

-3 -5V Bit

Permitted high signal range on LATCH/GATE/STATUS signals

11 30V

Typ. input current of the LATCH and/or GATE and/or STATUS signals at low level

0 mA

Typ. input current of the LATCH and/or GATE and/or STATUS signals at high level

4,0 mA

Max. number of bits on the counter input

32

Evaluation of counter pulses

1x, 2x, 4x

Phase offset between differential signals

90 deg

Phase offset tolerance

30 deg

Maximum cutoff frequency

5,0 MHz

Time constant of input filter on LATCH signal

50 µs

Time constant of input filter on GATE signal

50 µs

Time constant of input filter on STATUS signal

50 µs

Typ. processing time

0,1ms

Potential isolation between input/ output and periphery supply

Yes

Environmental data

Climatic suitability

EN 60068­2­1, EN 60068­2­14, EN 60068­2­2, EN 60068­2­30, EN 60068­2­78

Ambient temperature In accordance with the standard Temperature range

EN 60068­2­14 -40 ­ 70 °C

Storage temperature In accordance with the standard Temperature range

EN 60068­2­1/­2 ­40 ­ 70 °C

Climatic suitability In accordance with the standard Humidity

EN 60068­2­30, EN 60068­2­78 93 % r. h. at 40 °C

Condensation during operation

Short-term

EMC

EN 61000­4­2, EN 61000­4­3, EN 61000­4­4, EN 61000­4­5, EN 61000­4­6, EN 61000­6­2, EN 61000­6­4

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 1000,0 Hz

Amplitude

0,35 mm

Acceleration

5g

Broadband noise

In accordance with the standard

EN 60068-2-64

Frequency

5-500 Hz

Acceleration

1.9g_rms

Shock stress

In accordance with the standard EN 60068­2­27

EN 60068­2­27

Acceleration

15g

Duration

11 ms

In accordance with the standard

EN 60068­2­27

Acceleration

25g

Duration

6 ms

Max. operating height above sea level

5000 m

Airgap creepage

In accordance with the standard

EN 60664­1

OverVoltage category

II

Pollution degree

2

Protection type

In accordance with the standard

EN 60529

Mounting area (e.g. control cabinet)

IP54

Housing

IP20

Terminals

IP20

Material

Bottom

PC

Front

PC

Coding

PA

Mounting type

plug­in

Dimensions

Height

76,0 mm

Width

25,4 mm

Depth

60,2 mm

Weight

52 g

Mechanical coding

Type

F

Calor

Dark grey

There is an extended temperature range model, that admits operating temperature between -40ºC and +70ºC degrees. This model is used in the cabinets without temperature control.

Switches

Moxa EDS-408A-MM-SC-T

The EDS-408A are entry-level 8-port managed Ethernet switches designed especially for industrial applications and certified for SafetyNET p. The switches support a variety of useful management functions, such as Turbo Ring, Turbo Chain, ring coupling, port-based VLAN, QoS, RMON, bandwidth management, port mirroring, and warning by email or relay. The ready-to-use Turbo Ring can be set up easily using the web-based management interface, or with the DIP switches located on the top panel of the EDS-408A switches

Moxa Switch

Technical details for Moxa

Specification

8 Ethernet 10/100 ports: 2 100BaseFX Multi-Mode SC connector and 6 10/100BaseT(X) IEEE 802.3 for 10BaseT, IEEE 802.3u for 100BaseT(X) and 100BaseFX, IEEE 802.3x for Flow Control, IEEE 802.1D-2004 for Spanning Tree Protocol, IEEE 802.1w for Rapid STP, IEEE 802.1p for Class of Service, IEEE 802.1Q for VLAN Tagging

Management: IPv4/IPv6, SNMP v1/v2c/v3, LLDP, Port Mirror, RMON, DHCP Server/Client, DHCP Option 66/67/82, BootP, TFTP, SMTP, RARP, Telnet, Syslog, SNMP Inform, Flow Control, Back Pressure Flow Control

Filter: 802.1Q VLAN, Port-Based VLAN, GVRP, IGMP v1/v2, GMRP

Redundancy Protocols: STP, RSTP, Turbo Ring v1/v2, Turbo Chain

Time Management: SNTP, NTP Server/Client

Industrial Protocols: EtherNet/IP, Modbus/TCP, SafetyNET p

Performance

DHCP Option 82 for IP address assignment with different policies

Support EtherNet/IP, Modbus/TCP and PROFINET* protocols for device management and monitoring

EtherNet/IP EDS (Electronic Data Sheet) file, custom AOI (Add-On Instructions) and FactoryTalk® View faceplate available

PROFINET GSDML file and SIMATIC STEP 7 device icons available*

IGMP snooping and GMRP for filtering multicast traffic

Port-based VLAN, IEEE 802.1Q VLAN, and GVRP to ease network planning

QoS (IEEE 802.1p and TOS/DiffServ) to increase determinism

RMON for efficient network monitoring and proactive capability

SNMPv1/v2c/v3 for different levels of network management security

Bandwidth management to prevent unpredictable network status

Port mirroring for online debugging

Power Consumption

Input current

0.3A @24V

Input Voltage

24 VDC, redundant dual inputs

Operating voltage

12-45 VDC

Environmental data

Operating temperature

-40 to 75 ºC

Storage temperature

-40 to 85 ºC

Operating relative humidity

5 to 95% (condensing)

Mechanical Data

Dimensions

Height

53.6 mm

Width

135 mm

Height

105 mm

Weight

0.65 kg

Standards and Certifications

Standard safety certifications

UL 508, UL 60950-1*, CSA C22.2 No. 60950-1

Industrial safety certifications

UL 508 CSA 22.2 / 142 EN60204-1 EN61010-1 EN61131-2 EN61140

EMC

EN 55022/24

EMI

CISPR 22, FCC Part 15B Class A

EMS

IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8

Traffic Control

NEMA TS2

Marine

EDS-405A/408A, EDS-405A/408A 2 Fiber series: DNV, GL EDS-408A 3 Fiber series: DNV, GL, LR, ABS, NK

Schock

IEC 60068-2-27

Freefall

EC 60068-2-32

Vibration

IEC 60068-2-6

Hazardous Locations

UL/cUL Class 1 Division 2 Groups A/B/C/D, ATEX Zone 2 Ex nA nC IIC T4 Gc

Mean time between failures

Time

852421 hours