TMA Faults¶
Requested by: |
AURA |
---|---|
Doc. Code |
|
Editor: |
A. Izpizua |
Approved by: |
J. Garcia |
Introduction¶
This document contains the fault and warning list for each subsystem in the TMA. Additionally, it also contains a fault tree for each subsystem.
Fault list for each subsystem¶
This section contains the corresponding fault and warning list for each subsystem.
ACW¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
309 |
Critical Speed Limit |
Alarm |
The critical speed limit was violated |
Reset alarm |
310 |
Positive Software Limit |
Alarm |
The positive software limit is overcomed |
Disable the software limit using the settings and Reset alarm |
311 |
Negative Software Limit |
Alarm |
The negative software limit is overcomed |
Disable the software limit using the settings and Reset alarm |
312 |
Azimuth Cable Wrap Safety |
Alarm |
A safety issue has ocurred in the azimuth cable wrap module |
Check the safety cause and reset it if necessary then Reset alarm |
314 |
Critical Azimuth Deviation Limit |
Alarm |
The maximum allowed deviation between azimuth position and azimuth cable wrap position was overcomed |
Center the ACW to the Azimuth position and Reset alarm |
315 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
370 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
301 |
Speed Limit |
Warning |
The speed limit was violated |
306 |
Lubrication Level 1 Low |
Warning |
The motor 1 lubrication level is low |
307 |
Lubrication Level 2 Low |
Warning |
The motor 2 lubrication level is low |
313 |
Azimuth Deviation Limit |
Warning |
The allowed deviation between azimuth position and azimuth cable wrap position was overcomed |
Azimuth¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
100 |
TMAPXI-AXESPXI communication failure |
Alarm |
The communication between TMAPXI and AXESPXI is down. This was detected by the AXESPXI and the axis is in fault |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
101 |
SoftMotion Axis Fault |
Alarm |
The softmotion axis went to fault |
This is usually due to other fault, check other faults from the system Reset alarm |
102 |
STO |
Alarm |
The STO for the axis is active |
Check the safety cause and reset it if necessary then Reset alarm |
104 |
Overspeed |
Alarm |
Overspeed Alarm ocurred |
Reset alarm |
105 |
Axis Control Loop Finished Late |
Alarm |
The controller axis controller loop takes to much time to execute. The counter increases its value by 1000, when an issue is detected, decreasing by 1 each no problem iteration |
Check the temperature in the main cabinet AZ-0001, if it is too high it affects the performance of the CPU and makes the ethercat slow, ensure the cabinet is cooled and then reset alarm |
105 |
NoNewData |
Alarm |
New data does not arrive from EIB |
Check that the network is OK between the EIB and the AXIS PXI Reset alarm |
110 |
Positive Software limit |
Alarm |
The positive software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
111 |
Negative Software limit |
Alarm |
The negative software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
112 |
Positive Limit Switch |
Alarm |
The positive limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
112 |
Negative Limit Switch |
Alarm |
The negative limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
113 |
Negative Adjustable Software limit |
Alarm |
The negative adjustable software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
113 |
Positive Adjustable Software limit |
Alarm |
The positive adjustable software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
120 |
Critical AZCW Deviation Limit |
Alarm |
The maximum allowed deviation between azimuth cable wrap position and azimuth position was overcomed |
Move the ACW to the center of Azimuth Reset alarm and then do a home |
131 |
Negative Softmotion Software limit |
Alarm |
The negative software limit in the axis softmotion has been exceeded |
Disable the software limit using the settings and Reset alarm |
132 |
Positive Softmotion Software limit |
Alarm |
The positive software limit in the axis softmotion has been exceeded |
Disable the software limit using the settings and Reset alarm |
133 |
Following Error |
Alarm |
The axis detect and excessive deviation from the command |
Reset alarm |
136 |
Axis Fault |
Alarm |
Axis control algorithm detected a fault. Possible causes are: NoNewData, Too Many Drives in Fault, AXESPXI and TMAPXI comm fault or software error. Check if NoNewData or PXIs comm alarms are active, otherwise this means drives fault |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
160 |
Extrapolation Time Exceeded |
Alarm |
The defined extrapolation time was exceeded. |
Check that the CSC sends tracking commands Reset alarm |
180 |
Axis Communication Not Connected |
Alarm |
The status or telemetry task for the axis is NOT connected. |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
181 |
Axis Communication Tasks Not Running |
Alarm |
The status or telemetry task for the axis is not running. |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
190 |
Axis Externally Disabled |
Alarm |
The axis was disabled externally without using the enable command. |
This is caused by an STO Reset alarm and safety cause |
198 |
Software error in CW Tracking loop |
Alarm |
Cable wrap tracking command not sent. |
This is caused by the ACW being in fault, usually another alarm will be present from the ACW |
199 |
Internal Alarm in Azimuth OMT |
Alarm |
The description may vary, as this is a generic code for multiple alarms a subset of the possibilities is listed below |
Reset alarm |
Possible additional errors coming with 101
:
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
-8108 |
Software Error in axis management |
Alarm |
Tracking algorithm has an invalid output (NaN or Inf) |
Reset alarm |
-8109 |
Software Error in axis management |
Alarm |
Slewing algorithm has an invalid output (NaN or Inf) |
Reset alarm |
-8110 |
Software Error in axis management |
Alarm |
Slewing profile timing error |
Reset alarm |
Possible descriptions for alarm code 199
:
The request tracking speed is greater than the maximum allowed tracking speed.
Tracking command buffer is full. Continuous move command was ignored.
Zero speed setpoint received in a speed profile command.
Set initial position cannot be performed while the trajectory generator is enabled.
Speed setpoint higher than maximum speed.
Discrete move already being executed.
Command not allowed in current operation mode.
Operation cannot be changed while system is enabled.
System already enabled.
Slewing command detected during slewing move.
Trajectory generator is disabled. Command ignored.
The continuous command time setpoint is lower than current time.
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
104 |
Overspeed |
Warning |
Overspeed Warning ocurred |
105 |
NoNewData |
Warning |
New data does not arrive from EIB |
120 |
Active Drives |
Warning |
At least one drive is not active |
120 |
AZCW Deviation Limit |
Warning |
The maximum allowed deviation between azimuth cable wrap position and azimuth position was overcomed |
150 |
Past Time in Tracking Command |
Warning |
A tracking command was received with a past timestamp demand value. |
Azimuth Drives Thermal¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1601 |
ValveFaulty |
Alarm |
The valve of the drives temperature controller is faulty. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the valve |
1602 |
TemperatureTooHigh |
Alarm |
The temperature is too high. |
Reset alarm |
1603 |
ValveMovementTimeout |
Alarm |
The mixing valve takes too much time to get close the desired position. Check the valve status |
Reset alarm |
1604 |
NotEnoughSensors |
Alarm |
The minimum allowable temperature sensors in the group is reached and the temperature control could not work. Check temperature sensors |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1611 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1602 |
TemperatureTooLow |
Warning |
The temperature is too low. |
1604 |
1TemperatureSensorFailure |
Warning |
One of the temperature sensors in the group is failing. Check temperature sensors. |
1605 |
2TemperatureSensorFailure |
Warning |
Two of the temperature sensors in the group is failing. Check temperature sensors. |
1606 |
3TemperatureSensorFailure |
Warning |
Three of the temperature sensors in the group is failing. Check temperature sensors. |
1607 |
4TemperatureSensorFailure |
Warning |
Three of the temperature sensors in the group is failing. Check temperature sensors. |
Balancing¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1101 |
Critical Speed Limit |
Alarm |
The critical speed limit was violated. |
Reset alarm |
1102 |
Positive Position Limit |
Alarm |
The maximum position limit was violated. |
Disable the software limit using the settings and Reset alarm |
1103 |
Negative Position Limit |
Alarm |
The minimum position limit was violated. |
Disable the software limit using the settings and Reset alarm |
1110 |
Balancing System Safety |
Alarm |
A safety issue has occurred in the balancing system module. |
Check the safety cause and reset it if necessary then Reset alarm |
1111 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
1170 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1101 |
Speed Limit |
Warning |
The speed limit was violated. |
Azimuth Cabinet 0101¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1901 |
ValveFaulty |
Alarm |
The valve of the drives temperature controller is faulty. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the valve |
1902 |
TemperatureTooHigh |
Alarm |
The temperature is too high. |
Reset alarm |
1903 |
ValveMovementTimeout |
Alarm |
The mixing valve takes too much time to get close the desired position. Check the valve status |
Reset alarm |
1904 |
NotEnoughSensors |
Alarm |
The minimum allowable temperature sensors in the group is reached and the temperature control could not work. Check temperature sensors |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1911 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1902 |
TemperatureTooLow |
Warning |
The temperature is too low. |
1904 |
1TemperatureSensorFailure |
Warning |
One of the temperature sensors in the group is failing. Check temperature sensors. |
CCW¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1002 |
Positive Limit Switch Pressed |
Alarm |
The positive limit switch is pressed |
Disable the software limit using the settings and Reset alarm |
1003 |
Negative Limit Switch Pressed |
Alarm |
The negative limit switch is pressed |
Disable the software limit using the settings and Reset alarm |
1009 |
Critical Speed Limit |
Alarm |
The critical speed limit was violated |
Reset alarm |
1010 |
Positive Software Limit |
Alarm |
The positive software limit is overcomed |
Disable the software limit using the settings and Reset alarm |
1011 |
Negative Software Limit |
Alarm |
The negative software limit is overcomed |
Disable the software limit using the settings and Reset alarm |
1012 |
Camera Cable Wrap Safety |
Alarm |
A safety issue has ocurred in the camera cable wrap module |
Check the safety cause and reset it if necessary then Reset alarm |
1070 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1001 |
Speed Limit |
Warning |
The speed limit was violated |
1006 |
Lubrication Level 1 Low |
Warning |
The motor 1 lubrication level is low |
1007 |
Lubrication Level 2 Low |
Warning |
The motor 2 lubrication level is low |
Elevation¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
400 |
TMAPXI-AXESPXI communication failure |
Alarm |
The communication between TMAPXI and AXESPXI is down. This was detected by the AXESPXI and the axis is in fault |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
401 |
SoftMotion Axis Fault |
Alarm |
The softmotion axis went to fault |
This is usually due to other fault, check other faults from the system Reset alarm |
402 |
STO |
Alarm |
The STO for the axis is active |
Check the safety cause and reset it if necessary then Reset alarm |
404 |
Overspeed |
Alarm |
Overspeed Alarm ocurred |
Reset alarm |
405 |
Axis Control Loop Finished Late |
Alarm |
The controller axis controller loop takes to much time to execute. The counter increases its value by 1000, when an issue is detected, decreasing by 1 each no problem iteration |
Check the temperature in the main cabinet AZ-0001, if it is too high it affects the performance of the CPU and makes the ethercat slow, ensure the cabinet is cooled and then reset alarm |
405 |
NoNewData |
Alarm |
New data does not arrive from EIB |
Check that the network is OK between the EIB and the AXIS PXI Reset alarm |
410 |
Positive Software limit |
Alarm |
The positive software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
411 |
Negative Software limit |
Alarm |
The negative software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
412 |
Negative Limit Switch |
Alarm |
The negative limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
412 |
Negative Operational Limit Switch |
Alarm |
The negative Operational limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
412 |
Positive Limit Switch |
Alarm |
The positive limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
412 |
Positive Operational Limit Switch |
Alarm |
The positive Operational limit switch has been reached by axis |
Disable the software limit using the settings and Reset alarm |
413 |
Positive Adjustable Software limit |
Alarm |
The positive adjustable software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
413 |
Negative Adjustable Software limit |
Alarm |
The negative adjustable software limit has been exceeded |
Disable the software limit using the settings and Reset alarm |
431 |
Negative Softmotion Software limit |
Alarm |
The negative software limit in the axis softmotion has been exceeded |
Disable the software limit using the settings and Reset alarm |
432 |
Positive Softmotion Software limit |
Alarm |
The positive software limit in the axis softmotion has been exceeded |
Disable the software limit using the settings and Reset alarm |
433 |
Following Error |
Alarm |
The axis detect and excessive deviation from the command |
Reset alarm |
436 |
Axis Fault |
Alarm |
Axis control algorithm detected a fault. Possible causes are: NoNewData, Too Many Drives in Fault, AXESPXI and TMAPXI comm fault or software error. Check if NoNewData or PXIs comm alarms are active, otherwise this means drives fault |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
460 |
Extrapolation Time Exceeded |
Alarm |
The defined extrapolation time was exceeded. |
Check that the CSC sends tracking commands Reset alarm |
480 |
Axis Communication Not Connected |
Alarm |
The status or telemetry task for the axis is NOT connected. |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
481 |
Axis Communication Tasks Not Running |
Alarm |
The status or telemetry task for the axis is not running. |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
490 |
Axis Externally Disabled |
Alarm |
The axis was disabled externally without using the enable command. |
This is caused by an STO Reset alarm and safety cause |
499 |
Internal Alarm in Azimuth OMT |
Alarm |
The description may vary, as this is a generic code for multiple alarms a subset of the possibilities is listed below |
Reset alarm |
Possible additional errors coming with 401
:
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
-8108 |
Software Error in axis management |
Alarm |
Tracking algorithm has an invalid output (NaN or Inf) |
Reset alarm |
-8109 |
Software Error in axis management |
Alarm |
Slewing algorithm has an invalid output (NaN or Inf) |
Reset alarm |
-8110 |
Software Error in axis management |
Alarm |
Slewing profile timing error |
Reset alarm |
Possible descriptions for alarm code 499
:
The request tracking speed is greater than the maximum allowed tracking speed.
Tracking command buffer is full. Continuous move command was ignored.
Zero speed setpoint received in a speed profile command.
Set initial position cannot be performed while the trajectory generator is enabled.
Speed setpoint higher than maximum speed.
Discrete move already being executed.
Command not allowed in current operation mode.
Operation cannot be changed while system is enabled.
System already enabled.
Slewing command detected during slewing move.
Trajectory generator is disabled. Command ignored.
The continuous command time setpoint is lower than current time.
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
404 |
Overspeed |
Warning |
Overspeed Warning ocurred |
405 |
NoNewData |
Warning |
New data does not arrive from EIB |
420 |
Active Drives |
Warning |
At least one drive is not active |
450 |
Past Time in Tracking Command |
Warning |
A tracking command was received with a past timestamp demand value. |
Elevation Drives Thermal¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1701 |
ValveFaulty |
Alarm |
The valve of the drives temperature controller is faulty. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the valve |
1702 |
TemperatureTooHigh |
Alarm |
The temperature is too high. |
Reset alarm |
1703 |
ValveMovementTimeout |
Alarm |
The mixing valve takes too much time to get close the desired position. Check the valve status |
Reset alarm |
1704 |
NotEnoughSensors |
Alarm |
The minimum allowable temperature sensors in the group is reached and the temperature control could not work. Check temperature sensors |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1711 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1702 |
TemperatureTooLow |
Warning |
The temperature is too low. |
1704 |
1TemperatureSensorFailure |
Warning |
One of the temperature sensors in the group is failing. Check temperature sensors. |
1705 |
2TemperatureSensorFailure |
Warning |
Two of the temperature sensors in the group is failing. Check temperature sensors. |
1706 |
3TemperatureSensorFailure |
Warning |
Three of the temperature sensors in the group is failing. Check temperature sensors. |
Encoder System¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
702 |
Azimuth encoder heads bellow critical value |
Alarm |
The available encoder heads do not allow to continue the operation |
Check the tape and clean if necessary Reset alarm |
704 |
Elevation encoder heads bellow critical value |
Alarm |
The available encoder heads do not allow to continue the operation |
Check the tape and clean if necessaryReset alarm |
706 |
Frames loss |
Alarm |
UPD receiving data loop is loosing frames. The frames are not consecutive. |
Check the ethernet connection between the EIB and the PXI Reset alarm |
708 |
Received Data not OK |
Alarm |
Not all configured data packets are received from EIB or checksum is not valid |
Reset alarm |
710 |
Bad format udp packet |
Alarm |
Data received in upd port does not well formatted. The amount of bytes is not corresponding to configured data packet number for EIB |
Reset alarm |
711 |
UDP timeout |
Alarm |
Encoder UPD loop does not receive any data in 500 ms |
Reset alarm |
710 |
Timeout |
Alarm |
Depends on the command in execution |
Depends on the command faulted |
Warning list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
701 |
Azimuth lost encoder heads |
Warning |
One or more encoder heads are lost, but the system can continue working |
- |
703 |
Elevation lost encoder heads |
Warning |
One or more encoder heads are lost, but the system can continue working |
- |
705 |
Frames loss |
Warning |
UPD receiving data loop is loosing frames. The frames are not consecutive. |
- |
707 |
Received Data not OK |
Warning |
Not all configured data packets are received from EIB or checksum is not valid |
- |
709 |
Bad format udp packet |
Warning |
Data received in upd port does not well formatted. The amount of bytes is not corresponding to configured data packet number for EIB |
- |
755 |
Reference mark error |
Warning |
Reference mark calculation error for heads: failed head names.Possible a reference mark is missing |
Check the tape and clean if necessary |
756 |
Not all heads have a valid reference |
Warning |
When calculating the head reference value, the heads failed head names failed. They will not be used for absolute position calculation |
Try homing again. Some positions are badly calculated for azimuth, the calculated position is 360 deg away from the actual position, and can’t not be used |
Locking Pin¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1401 |
Locking Pin Safety |
Alarm |
A safety issue has occurred in the locking pin module. |
Check the safety cause and reset it if necessary then Reset alarm |
1402 |
Critical Speed Limit |
Alarm |
The critical speed limit was violated. |
Reset alarm |
1403 |
Position Negative Limit |
Alarm |
The Minimum position was violated |
Disable the software limit using the settings and Reset alarm |
1404 |
Position Positive Limit |
Alarm |
The maximum position was violated |
Disable the software limit using the settings and Reset alarm |
1411 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
1470 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1402 |
Speed Limit |
Warning |
The speed limit was violated. |
Main Axis¶
These relate to both Azimuth and Elevation but are covered in a separated section as they are single affecting both.
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
55 |
Axis CMD Writer |
Alarm |
Axis command writer has issue |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
56 |
Axis CMDs not connected |
Alarm |
Axis command connection is down |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
57 |
OSSAlarm |
Alarm |
The OSS is in Fault state |
Reset alarm |
58 |
Phase Power Supply Alarm |
Alarm |
The Phase Power Supply, supply for main axis, is in fault state |
Reset alarm |
65 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
51 |
Phase drives status not connected |
Warning |
Phase drives status connection is down |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
52 |
Phase drives status reader |
Warning |
Phase drives status task has an issue |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
53 |
Phase drives telemetry not connected |
Warning |
Phase drives telemetry connection is down |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
54 |
Phase drives telemetry reader |
Warning |
Phase drives telemetry reader task has an issue |
Reset alarm, if this doesn’t work reboot the AXES PXI and then reset the alarm |
Main Cabinet (AZ-0001)¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1301 |
Cabinet Fan Faulty |
Alarm |
The heat exchanger fan is faulty. |
Reset alarm, if persistent check the cabinet fan |
1302 |
Cabinet Heater Faulty |
Alarm |
The cabinet heater is faulty. |
Reset alarm, if persistent check the cabinet heater |
1303 |
Cabinet Valve Faulty |
Alarm |
The cabinet valve is faulty. |
Reset alarm, if persistent check the cabinet valve |
1304 |
Internal Temperature Sensor 1 Failed |
Alarm |
The temperature sensor that measures the internal temperature in the main cabinet (1) has failed. Its value is not valid. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1305 |
Internal Temperature Sensor 2 Failed |
Alarm |
The temperature sensor that measures the internal temperature in the main cabinet (2) has failed. Its value is not valid. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1306 |
Surface Temperature Sensor Failed |
Alarm |
The temperature sensor that measures the surface temperature in the main cabinet has failed. Its value is not valid. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1312 |
Backup Temperature Sensor Failed |
Alarm |
The backup temperature sensor used when RMC not working failed. If the RMC controller communication is lost, the backup hysteresis based controller will not work. |
Change the ethercat line to configuration and back to active then. Reset alarm, if persists check the sensors |
1313 |
RMC connection error |
Alarm |
The connection with the RMC controller was lost. The system is controlled through an hysteresis regulator. |
Reset alarm, if persistent check the connection to the RMC, the Watlow temperature controller |
1350 |
Critical Temperature Drop |
Alarm |
Cabinet Temperature decreased below critical limit. |
Reset alarm |
1351 |
Critical Temperature Increase |
Alarm |
Cabinet Temperature increased above critical limit. |
Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1308 |
Temperature Drop |
Warning |
Cabinet Temperature decreased below limit. |
1309 |
Temperature Increase sensor 1 |
Warning |
Cabinet Temperature increased above limit in sensor 1 |
1310 |
Surface Temperature Drop |
Warning |
Surface temperature decreased below limit. |
1311 |
Surface Temperature Increase |
Warning |
Surface temperature increased beyond limit. |
1314 |
Temperature Increase sensor 2 |
Warning |
Cabinet Temperature increased above limit in sensor 2 |
Mirror Covers¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
901 |
Mirror Cover Safety |
Alarm |
A safety issue has occurred in the mirror cover module. |
Check the safety cause and reset it if necessary then Reset alarm |
903 |
Critical Speed Limit |
Alarm |
This event triggers if the parameter “Critical Max Motor Velocity” is exceeded. |
Reset alarm |
908 |
ColisionEvent |
Alarm |
This event triggers if any MC are going to collision. |
Check visually that the mirror covers are being deployed properly, they must move two at a time and the first two must be completely deployed or retracted, then Reset alarm |
911 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
970 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
904 |
Speed Limit |
Warning |
This event triggers if the parameter “Motor Max Velocity” is exceeded. |
Mirror Cover Locks¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1501 |
Mirror Cover Safety |
Alarm |
A safety issue has occurred in the mirror cover module. |
Check the safety cause and reset it if necessary then Reset alarm |
1503 |
Critical Speed Limit |
Alarm |
This event triggers if the parameter “Critical Max Motor Velocity” is exceeded. |
Reset alarm |
1511 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
1570 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1504 |
Speed Limit |
Warning |
This event triggers if the parameter “Motor Max Velocity” is exceeded. |
Main Power Supply¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
600 |
MaxCurrent |
Alarm |
The maximum allowed current was exceed. |
Reset alarm |
601 |
MinVoltage |
Alarm |
The minimum allowed voltage was lost. |
Reset alarm, if persists check here |
602 |
Main Power Supply Safety |
Alarm |
A safety issue has occurred in the Main Power Supply module. |
Check the safety cause and reset it if necessary then Reset alarm |
611 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
600 |
MaxCurrent |
Warning |
The maximum allowed current was exceed. |
601 |
MinVoltage |
Warning |
The minimum allowed voltage was lost. |
OSS¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
801 |
Observation Sequence |
Alarm |
The OSSs observation sequence returned an alarm |
Reset alarm |
802 |
Cooling System |
Alarm |
The OSSs cooling system returned an alarm |
Reset alarm |
803 |
Main Pump System |
Alarm |
The OSSs main pump system returned an alarm |
Reset alarm |
804 |
Circulation System |
Alarm |
The OSSs circulation system returned an alarm |
Reset alarm |
806 |
Connection Lost |
Alarm |
The connection with the OSS has been lost |
Check connection with the OSS Reset alarm, if persistent reboot AUX PXI |
810 |
OSS Malfunction |
Alarm |
A safety issue has occurred in the OSS |
Check the safety cause and reset it if necessary then Reset alarm |
811 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
812 |
Cabinet AZ_OS_CBT_5001 High temperature |
Alarm |
The temperature of the Cabinet AZ_OS_CBT_5001 is too high |
Reset alarm |
813 |
Cabinet AZ_OS_CBT_5001 Low temperature |
Alarm |
The temperature of the Cabinet AZ_OS_CBT_5001 is too Low |
Reset alarm |
814 |
Cabinet EL_OS_CBT_5001 High temperature |
Alarm |
The temperature of the Cabinet EL_OS_CBT_5001 is too high |
Reset alarm |
815 |
Cabinet EL_OS_CBT_5001 Low temperature |
Alarm |
The temperature of the Cabinet EL_OS_CBT_5001 is too Low |
Reset alarm |
816 |
Cabinet EL_OS_CBT_5002 High temperature |
Alarm |
The temperature of the Cabinet EL_OS_CBT_5002 is too high |
Reset alarm |
817 |
Cabinet EL_OS_CBT_5002 Low temperature |
Alarm |
The temperature of the Cabinet EL_OS_CBT_5002 is too Low |
Reset alarm |
818 |
Emergency Stop |
Alarm |
Emergency Stop performed in the OSS |
Check the safety cause and reset it if necessary then Reset alarm |
819 |
Hard Stop |
Alarm |
Hard Stop performed in the OSS |
Check the safety cause and reset it if necessary then Reset alarm |
821 |
OSS Modbus fail |
Alarm |
The Modbus communication with the OSS is down |
Check connection with the OSS Reset alarm, if persistent reboot AUX PXI |
830 |
TemperatureTooHighAzCBT |
Alarm |
The temperature of the AZ OS CBT 5001 is too high. |
Reset alarm |
830 |
Soft Stop |
Alarm |
Soft Stop performed in the OSS |
Check the safety cause and reset it if necessary then Reset alarm |
831 |
TemperatureTooHighELCBT1 |
Alarm |
The temperature of the EL OS CBT 5001 is too high. |
Reset alarm |
832 |
TemperatureTooHighELCBT2 |
Alarm |
The temperature of the EL OS CBT 5002 is too high. |
Reset alarm |
860 |
Fault with detailed information |
Alarm |
This alarm is meant to give additional information to other faults. |
Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
830 |
TemperatureTooLowAzCBT |
Warning |
The temperature of the AZ OS CBT 5001 is too low. |
831 |
TemperatureTooLowELCBT2 |
Warning |
The temperature of the EL OS CBT 5002 is too low. |
831 |
TemperatureTooLowELCBT1 |
Warning |
The temperature of the EL OS CBT 5001 is too low. |
Deployable Platforms¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
1201 |
Critical Speed Limit |
Alarm |
This event triggers if the parameter “Platform Max Critical Velocity” is exceeded. |
Reset alarm |
1207 |
Deployable Platform Safety |
Alarm |
A safety issue has occurred in the deployable platform module. |
Check the safety cause and reset it if necessary then Reset alarm |
1211 |
Main Cabinet Off |
Alarm |
A fault ocurred at the Main Cabinet that is going to power off the cabinet. |
Reset the alarm from the main temperature cabinet and then Reset alarm |
1270 |
Bosch Power Supply Off |
Alarm |
The bosch power supply is off , therefore the systems that use the bosch drives cannot be used. |
Check that the bosch power supply is on then Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
1201 |
Speed Limit |
Warning |
This event triggers if the parameter “Platform Max Velocity” is exceeded. |
Modbus Auxiliary Boxes (TMA_AZ_DZ_CBT_0001, TMA_AZ_PD_CBT_0001, TMA_AZ_PD_TRM_0001, TMA_EL_PD_CBT_0001, TMA_EL_PD_CBT_0002)¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
2601 |
CabinetControllerNotOK |
Alarm |
The modbus temperature controller is in alarm. |
Check state of the controller and the temperature, then Reset alarm |
2602 |
ConnectionNotOK |
Alarm |
The modbus temperature controller connection is not okay. |
Check if the cabinet is on. If the cabinet is on check the communication to the controller, then Reset alarm |
2603 |
TemperatureTooHigh |
Alarm |
The temperature is out of the allowed band. |
Reset alarm |
Warning list¶
Code |
Name |
Type |
Description |
---|---|---|---|
2603 |
TemperatureTooLow |
Warning |
The temperature is too low. |
TopEndChiller¶
Fault list¶
Code |
Name |
Type |
Description |
Possible Solution |
---|---|---|---|---|
2201 |
0201 3 Way valve Failure |
Alarm |
Failure of the 0201 3 way valve |
Reset alarm |
2202 |
0202 3 Way valve Failure |
Alarm |
Failure of the 0202 3 way valve |
Reset alarm |
2203 |
ActionTimeout |
Alarm |
Timeout when power on/off or change to remote/local mode |
Reset alarm |
2204 |
Air Compressed Valve Failure |
Alarm |
Failure of the compressed air valve |
Reset alarm |
2205 |
CameraFansFailure |
Alarm |
The fans of the camera section have a failure |
Reset alarm |
2206 |
Electrical Cabinet 1 Control Failure |
Alarm |
Failure of the temperature controller in electrical cabinet 1 |
Reset alarm |
2207 |
Electrical Cabinet 2 Control Failure |
Alarm |
Failure of the temperature controller in electrical cabinet 2 |
Reset alarm |
2208 |
Electrical Cabinet 3 Control Failure |
Alarm |
Failure of the temperature controller in electrical cabinet 3 |
Reset alarm |
2209 |
Electrical Cabinet 4 Control Failure |
Alarm |
Failure of the temperature controller in electrical cabinet 4 |
Reset alarm |
2210 |
Heat Exchanger 1 Fan Failure |
Alarm |
Failure in the fans of the heat exchanger 1 |
Reset alarm |
2211 |
Heat Exchanger 2 Fan Failure |
Alarm |
Failure in the fans of the heat exchanger 2 |
Reset alarm |
2212 |
Humidity 0501 |
Alarm |
Humidity of the sensor 0501 out of range |
Reset alarm |
2213 |
Humidity 0502 |
Alarm |
Humidity of the sensor 0502 out of range |
Reset alarm |
2214 |
Humidity 0504 |
Alarm |
Humidity of the sensor 0504 out of range |
Reset alarm |
2215 |
Humidity 0505 |
Alarm |
Humidity of the sensor 0505 out of range |
Reset alarm |
2216 |
M2FansFailure |
Alarm |
The fans of the M2 section have a failure |
Reset alarm |
2217 |
PLC Malfunction |
Alarm |
The PLC for Top End chiller is working bad |
Reset alarm |
2218 |
Temperature 0501 |
Alarm |
Temperature of the sensor 0501 out of range |
Reset alarm |
2219 |
Temperature 0502 |
Alarm |
Temperature of the sensor 0502 out of range |
Reset alarm |
2220 |
Temperature 0504 |
Alarm |
Temperature of the sensor 0504 out of range |
Reset alarm |
2221 |
Temperature 0505 |
Alarm |
Temperature of the sensor 0505 out of range |
Reset alarm |
2222 |
Temperature 0506 |
Alarm |
Temperature of the sensor 0506 out of range |
Reset alarm |
2223 |
Temperature 0507 |
Alarm |
Temperature of the sensor 0507 out of range |
Reset alarm |
2224 |
Temperature Alarm Cabinet 1 |
Alarm |
Alarm temperature for electrical cabinet 1 |
Reset alarm |
2225 |
Temperature Alarm Cabinet 2 |
Alarm |
Alarm temperature for electrical cabinet 2 |
Reset alarm |
2226 |
Temperature Alarm Cabinet 3 |
Alarm |
Alarm temperature for electrical cabinet 3 |
Reset alarm |
2227 |
Temperature Alarm Cabinet 4 |
Alarm |
Alarm temperature for electrical cabinet 4 |
Reset alarm |
Fault tree for each subsystem¶
This section contains the corresponding fault tree for each subsystem.
Main Axes¶
This section contains the faults that affect both Azimuth and Elevation.
Azimuth individual fault tree¶
Here the faults that affect just Azimuth are displayed.
Elevation individual fault tree¶
Here the faults that affect just Elevation are displayed.
ACW¶
Encoder System¶
Main Power Supply¶
OSS¶
Azimuth Drives Thermal¶
Balancing¶
Azimuth Cabinet 0101¶
CCW¶
Elevation Drives Thermal¶
Locking Pin¶
Main Cabinet (AZ-0001)¶
Mirror Covers¶
Mirror Cover Locks¶
Deployable Platforms¶
Modbus Auxiliary Boxes (TMA_AZ_DZ_CBT_0001, TMA_AZ_PD_CBT_0001, TMA_AZ_PD_TRM_0001, TMA_EL_PD_CBT_0001, TMA_EL_PD_CBT_0002)¶
Top End Chiller¶