Deployable Platforms Screen¶
Deployable Platforms Screen – Main View¶
This screen displays the deployable platforms and enables their control.

Figure 2‑65. Deployable platforms screen - main view.
ITEM |
DESCRIPTION |
||
|---|---|---|---|
1 |
Displays the status, the section 1 position (in mm) and the section 2 position (in mm) of each platform. The box next to “run/alarm” lights up in the colour corresponding to the status of each platform. The green “retract” LEDs light up when the sections of the corresponding platforms are retracted. The green “extend” LEDs light up when the sections of the corresponding platforms are extended. The green “locked” LEDs light up when the corresponding extensions are locked. The green “inserted” LEDs light up when the corresponding extensions are inserted. |
||
2 |
Softkey “BOTH”: Selects both platforms. Softkeys “X-” and “X+”: Selects the corresponding platform. |
||
3 |
Softkey “ON”: Only turns on the system if no interlocks are active. Softkey “OFF”: Turns off the system. Softkey “RESET ALARM”: Resets the system from its current alarm state or resets the interlock if one exists. Softkey “EXTEND”: Extends the previously selected platform. Softkey “RETRACT”: Retracts the previously selected platform. Softkey “STOP”: Stops the movement. |
||
4 |
Softkeys “+” or “-”: Makes a movement at a constant speed in a positive or negative direction respectively. This sets the percentage of the default speed defined in the settings with the vertical slider. |
||
5 |
Softkeys “UNLOCK M2” and “UNLOCK M1M3”: Unlocks the extensions lateral locksstrong> of the corresponding platforms. M1M3 side extensions can only be extended if the “Mirror Cover” is retracted. Softkeys “LOCK M2” and “LOCK M1M3”: Lock the extensions of the corresponding platforms.
|
||
6 |
Accesses the screen Locking Pins General View Displays the status of the locking pins and turns on the LED with the corresponding colour:
|
||
7 |
Displays the status and position (in deg) of “Elevation”. Accesses the screen Elevation General View |
||
8 |
The blue softkey navigates between the active interlocks, if there is more than one. When an interlock is active, the top box is displayed in red. If no interlocks are active, the box will be green and the blue softkey cannot be pressed. |
Deployable Platforms Screen – Current Move¶
This screen shows a graph of the movement of the deployable platforms in real time.

Figure 2‑66. Deployable platforms screen - current view.
ITEM |
DESCRIPTION |
|---|---|
1 |
Displays a graph of the movement of the deployable platforms in real time. Softkey “FREEZE GRAPH”: Freezes the graph. Softkey “UPDATE GRAPH”: Allows the graph to be updated after being frozen. |
Deployable Platforms Screen – Move History¶
This screen displays and loads the last five movements of the deployable platforms, with number 1 being the last.

Figure 2‑67. Deployable platforms screen - move history.
ITEM |
DESCRIPTION |
|---|---|
1 |
Softkey “LOAD”: Loads the last five movements. Once the desired movement has been selected, it allows it to be displayed on the graph. |
Deploying the deployable platforms¶
There are two platforms: X- and X+, each have two sections and two extensions. X+ grants access for camera work.
Each section extends independently. See figure 2-2 in the Deployable platform technical specification document.
Platform section 1: the lower section, which supports section 2 during extension and retraction.
Platform section 2: the upper section of the platform.
The deploy sequence is:
Extend platform section 1
Extend platform section 2
The retract sequence is:
Retract platform section 2
Retract platform section 1
Precondition to deploy DP¶
TMA parked (drives off) and Elevation Locking pin inserted.
Procedure¶
To deploy the Deployable Platforms (DP):
Go to Home > Monitor and Control > Deployable Platform
Select
BOTHor one of the platforms sections (X-orX+).RESET ALARMif neededPower
ONPress
EXTENDPower
OFF, once they are fully deployed
Retracting the deployable platforms¶
Precondition to retract DP¶
TMA parked (drives off) and Elevation Locking pin inserted.
All extensions locking pins inserted and locked.
Procedure¶
To retract the Deployable Platforms (DP):
Go to Home > Monitor and Control > Deployable Platform
Select
BOTHor one of the platforms sections (X- or X+).RESET ALARMif neededPower
ONPress
RETRACTPower
OFF, once they are fully retracted.
Deployable Platform extensions management¶
Preconditions to manage the DP extensions¶
Platform completely deployed and powered OFF (idle state).
For the M1M3 DP extensions, the Mirror covers should be retracted (mirror exposed).
Procedure¶
Extending the extensions¶
From Home > Monitor and Control > Deployable Platform
Select
BOTHor one of the platforms sections (X-,X+).Unlock the extension you want to extend
Unlock M2 extensions: Press
UNLOCK M2Unlock M1M3 extensions: Press
UNLOCK M1M3Once unlocked the corresponding locked LED will be gray
From the deployable platforms on level 8:
Manually remove the pin on the extension to operate. You’ll see in the TMA EUI the inserted led will be gray
Manually extend the extensions.
Retracting the extensions¶
From the deployable platforms on level 8:
Manually retract the extensions
Manually insert the pin in the extension to operate. You’ll see in the TMA EUI the inserted led will be green.
From Home > Monitor and Control > Deployable Platform
Select
BOTHor one of the platforms sections (X-orX+).Lock the extension you want
Lock M2 extensions: Press
LOCK M2Lock M1M3 extensions: Press
LOCK M1M3Once locked the corresponding LED will be green.