Operating the EUI¶
Below you will find instructions for operating the EUI.
Starting the EUI¶
Open a terminal window.
ulimit -s 100000 cd /usr/local/natinst/LabVIEW-2018-64 ./labview
Open the
LSST_HMIs.lvproj
underRecent Projects
.Go to
Double click
HMIMain_EUI.vi
Find any missing libraries in the 2018 path.
Close any warning
Log in using HMI Credentials
Warning
If SAL kernel crashes computer must be restarted
Resetting Interlocks¶
Go to
On the right-most top-most column of the interface underneath Negative Pullcord click Reset
Go to
On the right-most top-most column of the interface under Control click Reset Alarm
On the row below in the same column underneath Cable Wrap Drive Selector click 2
You may see an error and timeout, this is fine repeat the step above
Then in the row above in Control click On
In the left-most column, underneath Drive 2 it should say Standstill with a box run/alarm with the color green above it.
Changing Settings¶
Go to
Locate the settings under the Monitoring column in the left-most top-most section.
Find the name of the setting you want to change under the Name column
Change the value in the Value column
In the column next to Value it should change to the color red for modified.
In the right-most top-most column under Control click Write under Apply Changes temporarily
In the column that changed to red it should become orange for written.